Fluke 709 Loop Calibrator Battery

小計(1 件)*

TWD52,931.00

(不含稅)

TWD55,577.55

(含稅)

Add to Basket
選擇或輸入數量
有庫存
  • 5 件準備從其他地點送貨
**需要更多嗎?**輸入您需要的數量,然後按一下「查看送貨日期」以查詢更多庫存和送貨詳細資訊。
單位
每單位
1 +TWD52,931.00

* 參考價格

RS庫存編號:
776-9529
Distrelec 貨號:
110-38-576
製造零件編號:
Fluke-709
製造商:
Fluke
透過選取一個或多個屬性來查找類似產品。
選取全部

品牌

Fluke

Product Type

Loop Calibrator

Accuracy

±0.01 %

Model Number

709

Resolution

1 μA

Battery Type

Rechargeable Nickel-Metal Hydride

Battery Life

20h

Power Source

Battery

Minimum Operating Temperature

0°C

Maximum Operating Temperature

40°C

Standards/Approvals

No

Height

150mm

Weight

980g

Length

54mm

Hazardous Area Certification

No

不適用

COO (Country of Origin):
CN

Fluke Loop Calibrator, ±0.01% Accuracy, 1 μA Resolution - Fluke-709


This loop calibrator is a handheld instrument for sourcing, simulating and measuring 4–20 mA process loops, including HART-enabled devices for on-site diagnostics. It is designed for technicians working in automation, electronics and mechanical maintenance who need a compact, portable tool to power loops, verify transmitter outputs and capture field data.

Features & Benefits


• ±0.01% accuracy for precise current verification and calibration
• 1 μA resolution enabling fine adjustment and tight tolerance checks
• Built-in 24V loop power for single-wire mA measurements
• Rechargeable NiMH power option supporting short-term field use
• Selectable 250 Ω resistor to Interface with HART transmitters
• Logging capacity of 9,800 records for extended diagnostic traces

Applications


• Suitable for commissioning and tuning 4–20 mA transmitters in plants
• Ideal for troubleshooting HART-enabled field instruments on site
• Used for validating loop integrity during preventive maintenance
• Can be used for recording process variables for control loop optimisation

What communications capability assists with HART device troubleshooting?


It includes a HART modem that supports common universal and common practice commands to read tags, sensor PVs, long tags and perform DAC trims and zero/gain adjustments.

How is logged data exported for analysis?


Recorded HART configurations and mA measurements can be uploaded via dedicated software to produce .csv or .txt files for further examination.

What environmental range allows safe operation in industrial settings?


The instrument operates between −10 °C and +55 °C with 10–95% non‑condensing humidity for typical plant conditions.

Which protection features prevent damage from wiring errors?


The unit provides over-voltage protection to 240 VAC and overload current protection at approximately 28 mA DC to reduce risk from fault conditions.

Supplied with

AC72-1 alligator clips (2), TL75 test leads, soft case, 6 AAA batteries (installed), product manual, quick reference guide, safety information