Better World

ABB System Pro M Compact S200 Miniature Circuit Breaker, 1-Pole, 63A, Type Z, 400V ac AC, 6 kA Breaking Capacity

小計(1 件)*

TWD3,982.00

(不含稅)

TWD4,181.10

(含稅)

Add to Basket
選擇或輸入數量
製造商存貨
  • 準備從 2026年6月08日 起發貨
**需要更多嗎?**輸入您需要的數量,然後按一下「查看送貨日期」以查詢更多庫存和送貨詳細資訊。
單位
每單位
1 +TWD3,982.00

* 參考價格

Better World

我們的 Better World 產品系列可讓您輕鬆選擇值得信賴的環保產品。 點擊此處了解更多。

RS庫存編號:
237-3224
製造零件編號:
2CDS251103R0608
製造商:
ABB
透過選取一個或多個屬性來查找類似產品。
選取全部

品牌

ABB

Number of Poles

1

Product Type

Miniature Circuit Breaker

Current Rating

63A

Tripping Characteristics

Type Z

Rated AC Voltage

400V ac

Mount Type

DIN Rail

Breaking Capacity

6kA

Range

System Pro M Compact

Series

S200

Terminal Type

Cage Terminal

IP Rating

IP40, IP20

Standards/Approvals

IEC/EN 60898-1, IEC/EN 60947-2

Depth

69mm

Width

35mm

Height

88mm

Better World Product

Yes

Better World Claim

Designed for Disassembly

Tripping Mechanism

Electromagnetic, Thermomagnetic

COO (Country of Origin):
DE

ABB S200 Series Miniature Circuit Breaker, 63A Current, 400V Rated AC Voltage - 2CDS251103R0608


This miniature circuit-breaker protects single-phase conductors against overloads and short circuits in residential, commercial and industrial control installations. It combines a delayed thermal element for overload protection with an electromagnetic trip for short-circuit interruption, and is intended for DIN-rail mounting in modular distribution equipment.

Features & Benefits


• 6 kA breaking capacity ensures controlled short-circuit interruption
• 63A rated current supports medium-duty feeder circuits
• Type Z tripping characteristic reduces nuisance trips on specific loads
• Thermomagnetic mechanism provides both overload and instant-trip protection
• Screw terminals enable secure conductor connections with 2.8 N·m torque
• Energy-limiting class 3 reduces let-through energy during faults

Applications


• Suitable for protection of motor-control circuits with inrush currents
• Ideal for distribution boards in light-industrial facilities
• used with automation panels requiring Compact overcurrent protection
• Can be used for single-pole protection of branch circuits in commercial buildings

What mounting options are available for installation?


It is designed for TH35 DIN-rail mounting compatible with TH35-15 and TH35-7.5 rails.

How does the contact position indication assist maintenance?


A red/green marker shows ON/OFF status, allowing quick Visual checks without testing.

What environmental limits should be observed during operation?


Ambient operating range is -25 to +55 °C with protection degrees IP20 (standard) and IP40 with cover.

What conductor sizes can be terminated into the device?


Terminals accept flexible and rigid conductors from 0.75 to 35mm² depending on type and ferrule use.