Fluke 789/771 GEAR Digital Multimeter, 0.4 V Min, 1000 V Max Tensilica LX6

小計(1 件)*

TWD84,562.00

(不含稅)

TWD88,790.10

(含稅)

Add to Basket
選擇或輸入數量
有庫存
  • 1 件準備從其他地點送貨
  • 加上 1 件從 2026年4月15日 起發貨
**需要更多嗎?**輸入您需要的數量,然後按一下「查看送貨日期」以查詢更多庫存和送貨詳細資訊。
單位
每單位
1 +TWD84,562.00

* 參考價格

RS庫存編號:
458-154
製造零件編號:
FLUKE-789/771 GEAR
製造商:
Fluke
透過選取一個或多個屬性來查找類似產品。
選取全部

品牌

Fluke

Product Type

Insulation Tester

Model Number

789/771 GEAR

Tester Type

Digital Multimeter

Maximum Test Voltage

1000V

Minimum Test Voltage

0.4V

Display Type

Digital

Test Current

20mA

Battery Type

Four AA alkaline

Power Source

Battery

Minimum Operating Temperature

-20°C

Maximum Operating Temperature

55°C

Safety Category Level

Tensilica LX6

Safety Category Voltage

1000V

Length

203mm

Standards/Approvals

CAT IV 600 V/CAT III 1000 V, IEC610101, Pollution Degree 2/IEC610102033

Height

5mm

Weight

600g

COO (Country of Origin):
US

Fluke Insulation Tester, 1000V Maximum Test Voltage, 20mA Test Current - FLUKE-789/771 GEAR


This insulation tester is a combined digital multimeter and mA loop calibrator designed for industrial troubleshooting and calibration tasks. It measures voltages, currents, resistance and frequency while also sourcing and simulating mA loops and providing loop power where required, enabling field technicians in automation, electronics and electrical trades to perform single‑tool diagnostics and verification.

Features & Benefits


• 0.05% accuracy on 0–20.000mA supports precise loop calibration
• 24V loop power supply delivers greater than 24V into 250ohm for loop tests
• True‑rms voltage measurement to 1000V for accurate AC readings
• 20mA drive with 24mA over‑range handles high‑test‑current scenarios
• Simultaneous mA and per cent‑of‑scale readout simplifies interpretation
• Four AA alkaline cells provide up to 140h measurement runtime

Applications


• Suitable for commissioning current‑loop transmitters and valves
• Ideal for maintenance checks on industrial control panels
• Used for field calibration of sensors and 4–20mA loops
• Can be used for fault‑finding on motor control and PLC inputs

What environmental range can it operate within for on‑site use?


It functions between −20°C and 55°C and survives storage down to −40°C.

How much continuous current can it measure without overheating?


It measures up to 1.000A with 0.440A continuous capability for extended tasks.

What protections exist for high‑voltage industrial environments?


The instrument is safety rated to CAT III 1000V and CAT IV 600V and meets IEC 61010‑1 and IEC 61010‑2‑033 requirements.

How is battery replacement handled in the field?


The battery compartment is externally accessible for quick swap of the four AA cells.

What measurement modes assist in capturing transient behaviour?


Min/Max/Average/Hold and relative modes are provided along with fast and slow auto‑ramp for output profiling.