Better World

Schneider Electric LUC DOL Starter, DOL, 690V ac, 0.25 kW, 3 Phase, IP20, IP40

小計(1 件)*

TWD3,545.00

(不含稅)

TWD3,722.25

(含稅)

Add to Basket
選擇或輸入數量
有庫存
  • 11 件準備從其他地點送貨
  • 加上 1 件從 2026年5月08日 起發貨
**需要更多嗎?**輸入您需要的數量,然後按一下「查看送貨日期」以查詢更多庫存和送貨詳細資訊。
單位
每單位
1 +TWD3,545.00

* 參考價格

Better World

我們的 Better World 產品系列可讓您輕鬆選擇值得信賴的環保產品。 點擊此處了解更多。

RS庫存編號:
272-482
Distrelec 貨號:
136-22-691
製造零件編號:
LUCA1XBL
製造商:
Schneider Electric
透過選取一個或多個屬性來查找類似產品。
選取全部

品牌

Schneider Electric

Power Rating

0.25kW

Product Type

DOL Starter

Sub Type

DOL

Number of Phases

3

Current Rating

1.4A

IP Rating

IP20, IP40

Number of Poles

3

Overall Length

66mm

Maximum Voltage

690V ac

Standards/Approvals

CSA C22.2 No. 14 type E, EN 60947-6-2, IEC 60947-6-2, UL 508 Type E

Hazardous Area Certification

ATEX

Overall Width

45mm

Series

LUC

Overall Depth

60mm

Better World Product

Yes

豁免

COO (Country of Origin):
FR

Schneider Electric LUC Series DOL Starter, 1.4A Current, 0.25kW Power Rating - LUCA1XBL


This DOL starter is a Compact three-phase motor starter designed for direct-on-line motor control and protection in industrial installations. It provides thermal-magnetic protection, phase-failure sensitivity and manual reset capability for low-power motors up to 0.25 kW at 400 to 440 V, operating on a 24V DC control supply. The unit is intended for use with compatible plug-in power bases and reversing contactor breakers in automated control systems.

Features & Benefits


• Thermal protection adjustable 0.35 to 1.4A for precise overload control
• Thermal overload class 10 for short delay before trip
• Thermal-magnetic trip threshold 14.2xIr for short-circuit discrimination
• 24V DC control circuit with 20 to 27V operational limits for secure actuation
• ATEX certification enabling use in specified hazardous areas
• IP20 front panel with IP40 external front protection for varied panel zones

Applications


• Suitable for motor starters in conveyor and pump control panels
• Ideal for small machine tool motor protection up to 0.25 kW
• Used with plug-in power bases LUB12/32/38 and LUB120/320/380 in control racks
• Can be used for reversing with compatible LU2B contactor breakers
• Suitable for installations requiring ATEX-certified control components

What control voltages will reliably operate the unit?


The control Coil is rated for 24V DC with an operational range of 20 to 27V and a dropout threshold near 14.5 V.

How quickly does the starter respond electrically during switching?


Operating times are approximately 70 MS to close and 35 MS to open under specified power base conditions.

What environmental extremes can it tolerate in service?


It operates between -25 to 70 °C, stores between -40 to 85 °C, and is rated for altitudes up to 2000 m.

How does the unit handle electromagnetic disturbances?


It meets immunity and emissions limits including 8 kV ESD, 10 V/m radiated field immunity, and fast transient classes up to 4 kV depending on circuit.

Note

'For use with' refers to a compatible power base in amps.

Warning

Schneider are in the process of amending the colour of the TeSys range, from White to Black. This means that the stock you receive could be either of these colours. Please be assured that the colour change in no way affects the Fit, Form or Function of the product.

相關連結