Schneider Electric LUC DOL Starter, DOL, 690V ac, 3 kW, 3 Phase, IP40

小計(1 件)*

TWD4,730.00

(不含稅)

TWD4,966.50

(含稅)

Add to Basket
選擇或輸入數量
有庫存
  • 17 件準備從其他地點送貨
  • 加上 17 件從 2026年12月11日 起發貨
**需要更多嗎?**輸入您需要的數量,然後按一下「查看送貨日期」以查詢更多庫存和送貨詳細資訊。
單位
每單位
1 +TWD4,730.00

* 參考價格

RS庫存編號:
272-454
Distrelec 貨號:
136-22-697
製造零件編號:
LUCA05FU
製造商:
Schneider Electric
透過選取一個或多個屬性來查找類似產品。
選取全部

品牌

Schneider Electric

Product Type

DOL Starter

Power Rating

3kW

Sub Type

DOL

Number of Phases

3

Current Rating

5A

IP Rating

IP40

Number of Poles

3

Overall Length

66mm

Maximum Voltage

690V ac

Standards/Approvals

CSA C22.2 No. 14 type E, UL 508 Type E, IEC 60947-6-2, EN 60947-6-2

Hazardous Area Certification

ATEX

Overall Width

45mm

Series

LUC

Overall Depth

60mm

豁免

Schneider Electric LUC Series DOL Starter, 5A Current, 3kW Power - LUCA05FU


This DOL starter is a Compact direct-on-line control unit designed to start and protect 3-phase motors in industrial installations. It integrates thermal-magnetic overload and short-circuit protection with phase loss and imbalance monitoring, and is intended for plug-in use on compatible power bases in automation and electrical control panels.

Features & Benefits


• 1.25 to 5A adjustable current protects motor windings
• 3kW at 690V AC delivers high-voltage motor starting capacity
• Class10 thermal release offers time-delayed overload response
• 110 to 240V AC or 110 to 220V DC Coil for flexible control supply
• ATEX certified for use in hazardous-area installations
• IP20 front and IP40 front-outside protection for panel mounting

Applications


• Suitable for starting 3-phase motors up to 3kW at 690V AC
• Ideal for control panels requiring hazardous-area compliant starters
• used with plug-in power bases such as LUB12 and LUB32
• Can be used for reversing contactor to breaker assemblies in motor control
• Suitable for machinery where phase-failure protection is required

What control supply voltages will operate the unit?


It accepts 110 to 240V AC and 110 to 220V DC with operation limits of 88 to 264V AC and 88 to 242V DC.

How quickly does it operate during switching events?


Typical operating times are 50 MS to close and 35 MS to open on compatible bases.

What environmental conditions can it tolerate in service?


It operates between -25 to 70°C, stores between -40 to 85°C, and is rated for altitudes up to 2000 m.

Which insulation and impulse voltage ratings apply to the control and main circuits?


Rated insulation voltage is 690V with a 6 kV impulse withstand Value and 400V SELV separation between circuits.

How does it behave electrically under overload trip?


The tripping threshold is 14.2xIr ±20% with thermal class 10 performance across 40 to 60 Hz.

Note

'For use with' refers to a compatible power base in amps.

Warning

Schneider are in the process of amending the colour of the TeSys range, from White to Black. This means that the stock you receive could be either of these colours. Please be assured that the colour change in no way affects the Fit, Form or Function of the product.