Siemens 6XV1830 Series Bus Cable 20 m Black Sheath PVC

小計(1 卷,共 20 米)*

TWD4,771.00

(不含稅)

TWD5,009.55

(含稅)

Add to Basket
選擇或輸入數量
有限的庫存
  • 2 件準備從其他地點送貨
**需要更多嗎?**輸入您需要的數量,然後按一下「查看送貨日期」以查詢更多庫存和送貨詳細資訊。
卷
每卷
每米*
1 +TWD4,771.00TWD238.55

* 參考價格

RS庫存編號:
203-3315
製造零件編號:
6XV1830-3FH10
製造商:
Siemens
透過選取一個或多個屬性來查找類似產品。
選取全部

品牌

Siemens

Product Type

Bus Cable

Cable Length

20m

Jacket Colour

Black

Outside Diameter

8mm

Conductor Type

Stranded

Minimum Operating Temperature

-40°C

Jacket Material

PVC

Maximum Operating Temperature

+60°C

Standards/Approvals

CE, RoHS Compliant

Voltage

80V

Fire Behaviour

Inflammable

Series

6XV1830

COO (Country of Origin):
DE

Siemens 6XV1830 Series Bus Cable, 20m Cable Length, 8mm Outside Diameter - 6XV1830-3FH10


This bus cable is a two-core underground PROFIBUS FC communication cable designed for buried installation and sold by the metre. It combines a stranded conductor and a screened construction with an extra protective outer cover to withstand mechanical stress when laid in the ground. The cable operates at low voltage and is suitable for industrial automation wiring where a robust, temperature-resistant link is required.

Features and Benefits:


• 80V RMS rated voltage providing safe low-voltage operation
• -40°C to +60°C ambient range enabling wide temperature resilience
• 150Ω characteristic impedance ensuring consistent signal integrity
• Overlapped foil and braided screen reducing external interference
• PE/PVC outer sheath protecting against mechanical damage

Applications


• Suitable for buried PROFIBUS FC installations in control networks
• Used with automation field devices requiring screened data links
• Ideal for factory floor cabling exposed to oil and water
• Used for outdoor runs where UV resistance is required

What conductor construction does it use?


It uses stranded conductors with PE insulation for flexibility and signal performance.

How does the cable manage electromagnetic interference?


It combines overlapped aluminium-clad foil with a tin-plated copper braid to provide a screened path for noise.

What mechanical protections are provided for ground installation?


An additional outer cover of PE provides abrasion resistance

the outer sheath must be removed for connector attachment.

How is signal attenuation specified across frequencies?


Attenuation is specified as maximum 0.0025 dB/m at 9.6kHz and 0.042 dB/m at 16 MHz.

What approvals and environmental conformities are declared?


It carries CE marking, RoHS conformity and EAC approval and meets fire classification EN13501-6 Fca.