Schneider Electric GV3 Series Thermal Circuit Breaker, 32A Current Rating, 690V Voltage Rating - GV3L32


This thermal circuit breaker is part of the TeSys range and is designed specifically for motor protection. With a current rating of 32A, it ensures reliable performance in various industrial applications. Its dimensions are 132mm x 55mm x 136mm, making it suitable for DIN rail mounting.

Features & Benefits


• Thermal-magnetic tripping mechanism offers enhanced protection
• Providing up to 100kA breaking capacity ensures system safety
• Rated operational voltage of 690V supports high-demand environments
• Compact design allows for efficient use of space in panels
• EverLink terminals facilitate secure connections and easy installation
• Suitable for isolation, improving system reliability during maintenance

Applications


• Used for motor circuit protection in industrial settings
• Ideal for installations requiring high-voltage safety compliance
• Suitable for panel needing compact circuit protection
• Employed in combination with other TeSys devices for optimal performance

What is the maximum motor power this device can handle?


It can handle up to 22kW at 690V AC, ensuring suitability for various motor applications.

What type of mounting is compatible with this circuit breaker?


This device is compatible with DIN rail mounting, accommodating 35mm symmetrical rails.

How do the breaking capacities vary across different voltages?


The breaking capacity is 6 kA at 690V AC, while it can reach 100 kA at lower voltages such as 230/240V and 400/415V AC.

What are the temperature tolerances for operation?


The acceptable ambient air temperature for operation ranges from -20°C to 60°C, allowing for versatile applications across environments.

What is its mechanical durability in terms of cycles?


This circuit breaker boasts a mechanical durability of up to 50,000 cycles, ensuring long-lasting performance in demanding conditions.