Eaton S811+R10P3S 600V ac, 100 HP, 3 Phase Soft Starter, IP20

小計(1 件)*

TWD108,596.00

(不含稅)

TWD114,025.80

(含稅)

Add to Basket
選擇或輸入數量
製造商存貨
  • 準備從 2026年12月21日 起發貨
**需要更多嗎?**輸入您需要的數量,然後按一下「查看送貨日期」以查詢更多庫存和送貨詳細資訊。
單位
每單位
1 +TWD108,596.00

* 參考價格

RS庫存編號:
120-310
製造零件編號:
168981 S811+R10P3S
製造商:
Eaton
透過選取一個或多個屬性來查找類似產品。
選取全部

品牌

Eaton

Power Rating

100HP

Product Type

Soft Starter

Number of Phases

3

IP Rating

IP20

Maximum Supply Voltage

600V ac

Overall Length

168.6mm

Maximum Operating Temperature

50°C

Overall Width

111.3mm

Standards/Approvals

CSA22.2-14-1995 CE IEC/EN 60947-4-2 UL 508 CCC GB14048 UL Category Control No.: NMFT UL CSA Class No.: 3211-06, 2411-01 CSA File No.: LR 353 CSA-C22.2 No. 14 CSA C-Tick UL File No.: E202571

Series

S811+R10P3S

Overall Depth

168.6mm

COO (Country of Origin):
DO

Eaton Soft Starter, 100 hp Power Rating, 105A Current Rating - 168981 S811+R10P3S


This soft starter is designed for three-phase motor control, catering for a power rating of up to 100 hp. The device operates at a voltage rating of 600 V AC and supports current ratings of 105 A, offering efficient soft start functionality. Constructed with an IP20 degree of protection, it measures 168.6mm in length, 111.3mm in width, and 201.2mm in height, weighing 4.8 kg. This robust starter meets several industry standards, including CSA, UL, and IEC/EN 60947-4-2.

Features & Benefits


• Integrated motor overload protection for enhanced safety
• Soft start function reduces mechanical stress on motors
• Internal bypass contacts for improved operational efficiency
• Modbus RTU Interface allows for easy communication
• Adjustable fault memory logs up to 10 fault occurrences
• Designed for ambient temperatures ranging from -30°C to 50°C

Applications


• Suitable for soft starting three-phase asynchronous motors
• Utilised in pumps and compressors requiring gradual acceleration
• Applied in industrial settings with variable load conditions
• Ideal for needing reliable overload monitoring

What are the ambient temperature requirements for operating this device?


The device operates effectively within a temperature range of -30°C to 50°C, ensuring reliable function in diverse environments.

How is the soft starter capable of limiting starting current?


It features a current limitation function that strategically reduces the initial current draw during motor start-up, maximising system protection.

Does it have built-in communication capabilities for integration with other systems?


Yes, it includes a Modbus RTU interface, simplifying connectivity with various automation systems for enhanced control.

Can this starter handle varying motor sizes?


It can accommodate motors rated up to 100 hp and supports various voltage conditions from 200 V to 600 V, making it versatile for different applications.

What kind of protection does this device offer against electrical faults?


The unit includes features such as overload monitoring and suppression of transients, ensuring that motors are safeguarded against electrical anomalies during operation.