Siemens Monitoring Relay, SPDT, DIN Rail, 24V ac 24 V dc

小計(1 件)*

TWD5,240.00

(不含稅)

TWD5,502.00

(含稅)

Add to Basket
選擇或輸入數量
有庫存
  • 4 件準備從其他地點送貨
**需要更多嗎?**輸入您需要的數量,然後按一下「查看送貨日期」以查詢更多庫存和送貨詳細資訊。
單位
每單位
1 +TWD5,240.00

* 參考價格

RS庫存編號:
175-2271
製造零件編號:
3RN2000-2AA30
製造商:
Siemens
透過選取一個或多個屬性來查找類似產品。
選取全部

品牌

Siemens

Product Type

Monitoring Relay

Contact Configuration

SPDT

Mount Type

DIN Rail

Power Consumption

0.5W

Terminal Type

Spring Terminal

IP Rating

IP20

Supply AC Voltage

24V ac

Supply DC Voltage

24 V dc

Contact Current

1A

Minimum Operating Temperature

-25°C

Maximum Operating Temperature

+60°C

Length

91.6mm

Series

3RN2

Width

17.5mm

Standards/Approvals

No

Height

100mm

COO (Country of Origin):
DE

Siemens 3RN2 Series Monitoring Relay, 24V Supply Voltage, 1A Contact Current - 3RN2000-2AA30


This monitoring relay is a Compact evaluation unit designed for thermistor motor protection in control panels. It operates from a 24V AC/DC supply and provides a single changeover contact with automatic reset and a tripped LED indication. The device mounts on a 35mm DIN rail using snap‑on or screw fastening and is intended for industrial installations requiring thermal sensing via bimetallic temperature switches.

Features and Benefits:


• 0.30W power loss reduces energy draw in continuous operation
• -25°C to 60°C operational range supports wide ambient conditions
• 1A DC contact current enables control of low‑power circuits
• Spring‑loaded terminals allow quick conductor insertion
• 5A switching element withstands transient load conditions

Applications


• Suitable for motor thermistor protection installations
• Ideal for control panels in industrial environments
• Used with bimetallic temperature switches for monitoring
• Can be used where Compact DIN rail mounting is required
• Suitable for systems needing automatic reset after trip

What surge immunity does the unit provide?


It offers 4kV surge voltage resistance and withstands conductor-to-earth surge up to 2kV.

How long will the relay switch contacts endure electrically?


At 24V AC under AC-15 duty the contact endurance is typically 100,000 operating cycles.

What conductor sizes are accepted by the terminals?


Solid conductors 0.5…4 mm² and finely stranded with end ferrules 0.5…2.5 mm² are supported.