Schneider Electric

Number of Poles

2

Current Rating

6A

Tripping Characteristics

Type C

Rated AC Voltage

440 V, 12 → 133 V, 220 → 240 V, 380 → 415V

Rated DC Voltage

100 → 133V

Breaking Capacity at Maximum Voltage Rating

10 kA

Range

Acti 9

Series

iC60H

Circuit Breaker Type

MCB

Width

36mm

Length

85mm

Mounting Style

DIN Rail Mount

Depth

78.5mm

Model Number

iC60H 2P 6A C

Better World Product

Yes

Better World Verification

Green Premium

Special Features

IP20 Terminal Protection

Reset Actuator Type

Rocker Switch

Tripping Mechanism

Thermal-Magnetic

Terminal Contact Type

Screw

COO (Country of Origin):
BG

A9F54206 Schneider Electric


This model has tripping curve type C that trips instantly at a rate of five to ten times its rated current. 2 pole breaker and a breaking capacity of 10 kA.

Features & Benefits


• Thermal-magnetic circuit breaker provides reliable protection
• 10 kA breaking capacity ensures safety during overloads
• IP20 terminal protection safeguards against accidental contact
• Screw terminal design facilitates easy and secure connections
• Dual-pole configuration allows for efficient circuit management
• Wide voltage ratings support various applications

Applications


• Used for protecting lighting circuits in residential buildings
• Suitable for industrial machinery requiring circuit control
• Ideal for residential and commercial electrical installations
• Compatible with automation systems needing reliable circuit protection

What type of connections does it support for wire termination?


The circuit breaker accommodates single terminal connections for both rigid and flexible wires, with sizes ranging from 1 to 25mm² for rigid and 1 to 16mm² for flexible conductors.

How do the thermal-magnetic tripping characteristics enhance performance?


The thermal-magnetic trip unit provides dual protection, detecting both overload conditions and short circuits, ensuring quick disconnection to prevent damage to electrical equipment.

What is the operational temperature range of this circuit breaker?


It operates effectively in a wide ambient air temperature range from -35°C to 70°C, making it suitable for various environmental conditions.

What level of electrical durability can be expected from this device?


It is designed for electrical durability of up to 10,000 cycles, ensuring long-term reliability in frequent operational environments.

How can this circuit breaker be safely maintained and accessed?


The device features a trip indicator for local signalling and provisions for padlocking, enhancing safety during maintenance and reducing the risk of accidental activation.

Standards

EN/IEC 60947-2, EN/IEC 60898-1.


Merlin Gerin – MCBs


Miniature Circuit Breakers; Contact Position indicated by switch levers