Schneider Electric Multi9 C60N Miniature Circuit Breaker, 3-Pole, 16 A, Type C, 240 V ac AC, 125 V dc DC, 30 kA Breaking

小計(1 件)*

TWD4,902.00

(不含稅)

TWD5,147.10

(含稅)

Add to Basket
選擇或輸入數量
有庫存
  • 14 件準備從其他地點送貨
**需要更多嗎?**輸入您需要的數量,然後按一下「查看送貨日期」以查詢更多庫存和送貨詳細資訊。
單位
每單位
1 +TWD4,902.00

* 參考價格

RS庫存編號:
214-2071
製造零件編號:
M9F11316
製造商:
Schneider Electric
透過選取一個或多個屬性來查找類似產品。
選取全部

品牌

Schneider Electric

Product Type

Miniature Circuit Breaker

Number of Poles

3

Tripping Characteristics

Type C

Breaking Capacity

30kA

Mount Type

Clip-on

Range

Multi9

Series

C60N

Terminal Type

Tunnel Terminal

IP Rating

IP20, IP40

Height

81mm

Standards/Approvals

EN/IEC 60947-2

Depth

72mm

Tripping Mechanism

Thermal Magnetic

COO (Country of Origin):
BG

Schneider Electric C60N Series Miniature Circuit Breaker, 16A Current, 240VAC Rated AC Voltage - M9F11316


This miniature circuit-breaker provides thermal-magnetic protection for three-phase distribution and DC networks in industrial installations. Designed for panel or DIN-rail mounting, it offers overcurrent interruption and selective tripping for load circuits while indicating contact position for straightforward status checks.

Features & Benefits


• Type C thermal-magnetic tripping for controlled inrush handling
• 30kA breaking capacity at low-voltage DC for high-fault clearing
• 10kA Icu at 415V AC for robust phase-to-phase protection
• Tunnel terminals accepting up to 25mm² conductors for secure connections
• Padlockable toggle to allow safe isolation during maintenance
• 20000 mechanical cycles for prolonged switching life

Applications


• Suitable for motor feeder protection with moderate starting currents
• Ideal for three-phase distribution boards in factories
• used with DC control supplies requiring high breaking capacity
• Can be used for machine-room isolation and maintenance tagging
• Suitable for industrial automation panel installations

What Terminal arrangements accommodate larger conductor sizes?


The unit uses tunnel-style terminals TOP or bottom that accept rigid, flexible and ferrule-terminated conductors up to 25mm² with a 14mm wire strip length and 2N·m tightening torque.

How does the breaker perform across different supply voltages?


It is rated for operation up to 240V AC between phases and accepts higher phase voltages at 415V and 440V AC, and is suitable for DC systems at voltages up to 125V.

What environmental limits affect installation locations?


It operates between -30 to 70°C, withstands relative humidity to 95% at 55°C, meets pollution degree 3, and offers IP20 protection or IP40 when installed in a modular enclosure.

How is serviceability and lifecycle described?


Electrical endurance is specified at 10000 cycles and mechanical endurance at 20000 cycles, with heat dissipation approximately 7.5W at 415V for a 16A load.