Watson Smith NPT 1/4 Female 2.5NL/min IP Converter, 4-20 mA input 0.2 bar to 2 bar
- RS庫存編號:
- 538-3782
- 製造零件編號:
- EX140 01PK4EE1
- 製造商:
- Watson Smith
小計(1 件)*
TWD31,693.00
(不含稅)
TWD33,277.65
(含稅)
庫存資訊目前無法存取 - 請稍後再回來查看
單位 | 每單位 |
|---|---|
| 1 + | TWD31,693.00 |
* 參考價格
- RS庫存編號:
- 538-3782
- 製造零件編號:
- EX140 01PK4EE1
- 製造商:
- Watson Smith
規格
產品概覽和技術數據資料表
法例與合規
產品詳細資訊
透過選取一個或多個屬性來查找類似產品。
選取全部 | 屬性 | 值 |
|---|---|---|
| 品牌 | Watson Smith | |
| Input Signal | 4-20 mA | |
| Product Type | IP Converter | |
| Maximum Flow Rate | 2.5NL/min | |
| Connection Size | NPT 1/4 Female | |
| Connection Thread Standard | NPT | |
| Overall Length | 116mm | |
| Minimum Outlet Pressure | 0.2bar | |
| IP Rating | IP66 | |
| Maximum Input Pressure | 10.3bar | |
| Maximum Outlet Pressure | 2bar | |
| Minimum Operating Temperature | -40°C | |
| Maximum Operating Temperature | 85°C | |
| Overall Width | 94mm | |
| Hazardous Area Certification | ATEX | |
| Standards/Approvals | Cenelec ATEX / SIRA 01ATEX1006 / SIRA 01ATEX2007X / SIRA 01ATEX4008X / FM APPROVED / CSA | |
| Overall Height | 161mm | |
| 選取全部 | ||
|---|---|---|
品牌 Watson Smith | ||
Input Signal 4-20 mA | ||
Product Type IP Converter | ||
Maximum Flow Rate 2.5NL/min | ||
Connection Size NPT 1/4 Female | ||
Connection Thread Standard NPT | ||
Overall Length 116mm | ||
Minimum Outlet Pressure 0.2bar | ||
IP Rating IP66 | ||
Maximum Input Pressure 10.3bar | ||
Maximum Outlet Pressure 2bar | ||
Minimum Operating Temperature -40°C | ||
Maximum Operating Temperature 85°C | ||
Overall Width 94mm | ||
Hazardous Area Certification ATEX | ||
Standards/Approvals Cenelec ATEX / SIRA 01ATEX1006 / SIRA 01ATEX2007X / SIRA 01ATEX4008X / FM APPROVED / CSA | ||
Overall Height 161mm | ||
豁免
- COO (Country of Origin):
- GB
Watson Smith I/P Converter
The Watson Smith I/P converter is a robust instrument with a flow rate less than 2.5nl/min, connection thread standard NPT female and 1/4in connection thread size. It implements electronic current-to-pressure conversion utilising advanced closed-loop operation to allow accurate high-resolution pressure control via a 4-20mA input signal. Fail-safe operation ensures that output pressure falls to zero on the loss of the input signal. I/P converters are electro-pneumatic instruments that will change pneumatic pressures in response to varying electrical current and voltage input signals. They have extensive application potential in both industrial and process systems, for control of cylinders, valves, valve positioners, relays, brakes and clutches. The converters can be mounted in control rooms or the field and have zero and span settings that are adjustable from the front face of the instrument. Failsafe converters are available which will cause the output pressure to fall below 15mbar (0.2 PSIG) in the event of power failure or loss of the input signal.
Note:
This converter should only be used with oil-free clean dry air filtered to 5μm or less.
*Inlet pressure must be at least 0.7bar above output pressure
Features and Benefits
ATEX-certified explosion-proof construction
Fail-safe operation
Field replaceable air filter
Jack socket for on-site monitoring
Certifications
EEx d IIC T4
IP66 rated
相關連結
- Watson Smith, 4-20 mA input 0.2 bar to 1 bar
- Watson Smith NPT 1/4 Female 1.75 L/min I/P & E/P Converters, 1 to 10 V input 0.14 bar to 8 bar
- Watson Smith Pneumatic Regulator -, 1/4 NPT 0.2 bar Manostat Precision Pressure Regulator
- Watson Smith NPT Pneumatic Regulator -, 1/4 NPT 0.2 bar Manostat Precision Pressure Regulator
- Watson Smith NPT Pneumatic Regulator -, 1/4 NPT 0.14 bar Manostat
- EMERSON – AVENTICS M12 120 L/min Pressure Regulator, 4 to 20 mA input 0.5 bar to 3 bar
- EMERSON – AVENTICS M12 120 L/min Pressure Regulator, 4 to 20 mA input 0.5 bar to 7 bar
- EMERSON – AVENTICS M12 120L/min Pressure Regulator, 0 to 10 V input -1 bar to -1 bar