Alpha Wire Alpha Essentials Communication & Control Control Cable, 5 Cores 24 AWG, Screened, 30 m, Slate Polyvinyl

小計(1 卷,共 30 米)*

TWD9,210.00

(不含稅)

TWD9,670.50

(含稅)

Add to Basket
選擇或輸入數量
庫存資訊目前無法存取 - 請稍後再回來查看
單位
每單位
每卷*
30 +TWD307.00TWD9,210.00

* 參考價格

RS庫存編號:
187-2046
製造零件編號:
6329 SL005
製造商:
Alpha Wire
透過選取一個或多個屬性來查找類似產品。
選取全部

品牌

Alpha Wire

Series

Alpha Essentials Communication & Control

Product Type

Control Cable

Number of Cores

5

Conductor Material

Tin Copper Wire

Jacket Material

Polyvinyl Chloride

Jacket Colour

Slate

Screened/Unscreened

Screened

Cable Length

30m

Outside Diameter

5.61mm

Voltage

300V

Minimum Operating Temperature

-20°C

Standards/Approvals

UL, CSA, CE

Maximum Operating Temperature

80°C

Hazardous Area Certification

No

American Wire Gauge

24AWG

Fire Behaviour

VW-1, FT4

Core Strands

7

Belden Alpha Essentials Communication & Control Series Control Cable, 30m Cable Length, 5 Cores - 6329 SL005


This control cable is a screened, five-core connection designed for industrial control and signal transmission in automation and electrical systems. It combines tinned copper conductors and a PVC outer sheath to deliver consistent performance across typical plant environments, operating between -20°C and 80°C.

Features & Benefits


• 300V rating provides safe low-voltage signal distribution
• Screened construction reduces electromagnetic interference on signals
• Tin copper 7-strand conductors improve flexing longevity
• VW-1 FT4 flame-retardant materials enhance fire performance
• Slate PVC jacket resists abrasion and environmental exposure
• 5-core configuration simplifies multi-signal cabling runs

**Applications**


• Suitable for programmable logic controller signal wiring
• Ideal for factory-floor motor control circuits
• Used with sensor arrays and actuator networks
• Can be used for panel interconnect and Terminal strip feeds
• Suitable for machine tool cabling where screening is required

What is the conductor construction and why does it matter for movement?


Each conductor is MADE from tinned copper composed of seven strands to balance conductivity with flexibility, reducing fatigue in repeated flexing applications.

How is the cable shield implemented and what electrical benefit does it provide?


The shield combines aluminium/Mylar tape with a tinned copper braid and a drain wire to provide a continuous earth path and lower shield resistance, improving noise rejection.

What printing and marking can be expected on the outer sheath?


The jacket carries manufacturer identification and cable type markings indicating conductor size, core count, screening and temperature rating for installation traceability.

What mechanical limits should installers observe during routing?


Follow a minimum bend radius of ten times the cable diameter and limit pull tension to the specified maximum to avoid conductor or jacket damage.

相關連結